초록 close

- In order to investigate the possibility of separating PD(partial discharge) and noises through the pulse analysis by use of a HFCT, pulse shapes measured by a resistive sensor and a HFCT were analyzed and adequate PA(pulse analysis) algorithms were studied. For the purpose, the HFPD detection and PA system has been developed. Also void discharges and air corona were adopted as the artificial defect and noises, respectively. As a result, it is possible to separate partial discharges and noises through the PA method using the 100kHz~20MHz frequency range HFCT. It is expected to apply the developed system to on-site PD measurements for the electric equipments.